8000 Amps Transformers

The transformer dimensions are shown below:

12 KVA Transformer 15” W x 12.5” H x 22” D (Photo for reference only)
12 KVA Transformer 15” W x 12.5” H x 22” D (Photo for reference only)

Customer requirement is shown below:

Specification:

  • Input: 600 VAC, 40 A, 1 PH, 60 Hz, P/N 5217L1
  • Output: 2 VAC, 8000 Amps, 24 hour duty cycle
  • Two transformer outputs are connected in parallel
  • Enclosure dimensions: 50″ H x 36″ W x 26″ D
  • Transformer Output bus bars are 6″ x 10″ x 3/4″
  • Transformer outputs are connected in parallel with 4″ x TBD x 3/4″
  • Four fans installed on the enclosure for cooling
  • Customer provides 120 VAC to the fans

The schematic diagram is shown below:

Schematic Diagram, P/N 5217L1
Schematic Diagram, P/N 5217L1

The transformer dimensions are shown below:

Transformer Dimensions: 15” W x 12.5” H x 22” D
Transformer Dimensions: 15” W x 12.5” H x 22” D

The lay out of the unit is shown below:

Components inside the enclosure
Components inside the enclosure