(714) 624-4740 quote@lcmagnetics.com

THREE PHASE HIGH CURRENT TRANSFORMER
300 KVA, OUTPUT 188 VAC, 532 AMPS, P/N 19239

Specifications:

  • High Current Transformer, 300 KVA, 3 PH, 60 Hz, P/N 19239
  • Primary: 460 VAC L-L, 377 Amps, Wye with a neutral
  • Secondary: (TBD) VAC L-L, 532 Amps, Open Delta, see Table A
  • Copper winding construction
  • Primary and secondary Copper bus bars are 2” x 1/4” with one hole
  • Open core and coil: 38”H x 46”W x 25”D approximately
  • Estimated weight: 3000 lbs.

The photo of the transformer is shown below:

 

 

Table A

Primary (460 VAC L-L) Secondary Open Delta
A, A, A 226 VAC L-L
B, B, B 207 VAC L-L
C, C, C 188 VAC L-L

 

The schematic diagram is shown below:

 

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.